Private previewCandidate · Draft · Noindex. Reference configuration; supply and public media use require confirmation.

LCP-000034 / Product configuration

MEMS Pressure Transmitter for Liquid Cooling — Danfoss DST P140 Reference

A separately pictured DST P140 pressure-transmitter series reference for liquid-cooling data centers, with MEMS and sealed stainless media-interface construction. Range, signal, connector and accuracy remain order-code dependent.

Gauge pressure range
0 to 10 bar
Output signal
4 to 20 mA
Process and electrical connections
G 1/4 A male pressure connection to ISO 1179-2; M12 × 1 electrical connection
Supply voltage
8 to 28 VDC
Wetted materials
AISI 304L and AISI 316L listed for wetted parts

Technical selection

Specifications and configuration

Reference — Danfoss DST P140 pressure transmitter series

ParameterDocumented value / configuration
Documented applicationLiquid-cooling data-center pressure monitoringConditions: scope: Series application statement; exact order-code specification not established
Sensing and body designMEMS sensing technology with stainless-steel design and hermetically sealed media interfaceConditions: scope: Series description; wetted alloy and pressure range require order code
Diagnostic optionAutomatic sensor-failure detection described as an optional diagnostic capabilityConditions: scope: Optional, not claimed on all DST P140 variants

Reference — Danfoss DST P140 075G4027

ParameterDocumented value / configuration
Gauge pressure range0 to 10 barConditions: scope: Old manufacturer datasheet copy; current Danfoss Design Center also lists 0–10 bar gauge for this code. Measuring span, not overpressure or site supply rating
Output signal4 to 20 mAConditions: scope: Current Danfoss Design Center also lists 4–20 mA for this exact code
Process and electrical connectionsG 1/4 A male pressure connection to ISO 1179-2; M12 × 1 electrical connectionConditions: scope: Current Danfoss Design Center independently lists the same code's G 1/4-A and M12 × 1 interfaces; mating connector is a separate installation input
Supply voltage8 to 28 VDCConditions: scope: Series data sheet specification for the 4–20 mA option; current exact-code Danfoss Design Center lists 8–28 V DC

Reference — Danfoss DST P140 series

ParameterDocumented value / configuration
Wetted materialsAISI 304L and AISI 316L listed for wetted partsConditions: scope: Current Danfoss Design Center shows 304L/316L for 075G4027; coolant and seal compatibility still require application review

Manufacturer series reference. Confirm the exact order code, mating parts and stated conditions for the quoted configuration.

Overview

The DST P140 is a manufacturer-documented pressure-transmitter series for liquid-cooling data-center circuits and other water-related duties. This catalog entry represents the pictured sensor series, not an invented site model or a confirmed supply agreement with Danfoss.

Construction and interfaces

The official series page describes MEMS sensing, stainless-steel construction and a hermetically sealed media interface. The pictured transmitter establishes its physical product class, while wetted alloy, process connector and electrical connector still depend on the selected order code.

Selection

Danfoss order code 075G4027 is listed for 0–10 bar gauge measurement, 4–20 mA output, G 1/4 A male process connection to ISO 1179-2 and M12 × 1 electrical connection. The data sheet lists 8–28 V DC supply for the 4–20 mA version. Confirm the actual code, mating cable, gauge reference and installed measurement point before specifying it.

Configuration options

Other DST P140 codes have different ranges and electrical or pressure connections; they are not interchangeable merely because they share the series name. For 075G4027, the manufacturer lists 304L/316L wetted parts. State the connector, coolant, temperature and any calibration or diagnostic requirements on the RFQ.

Application limits

The order-code values are from a Danfoss data sheet preserved by a distributor and cross-checked against Danfoss's indexed Design Center entry. The current direct datasheet URL returned 404 and the product page could not be collected by the restricted fetcher, so recheck the current revision before purchasing. The series photo does not prove the pictured unit's exact code; accuracy and coolant suitability remain conditioned on the final configuration.