Private previewCandidate · Draft · Noindex. Reference configuration; supply and public media use require confirmation.

Liquid cooling component family

Custom Manifold Assemblies

A candidate family page for drawing-led manifold bodies, attached components, and assembly validation.

Supply return
Rack-mounted distribution routes coolant to individual servers.
Port count
A 44-branch manifold is used only as a stated simulation example, not as a family default.
Material
PVDF
Flow distribution
Manufacturer describes uniform volume flow across outlet ports; validation remains configuration-specific.
Pressure drop
Simulation limit below 50 mbar per manifold

Technical selection

Specifications and configuration

Reference — CoolIT Systems — family reference

ParameterDocumented value / configuration
Supply returnRack-mounted distribution routes coolant to individual servers.
MountingMounted to server racks.

Reference — Parker Hannifin — family reference

ParameterDocumented value / configuration
Integrated componentsRepresentative manifold assemblies integrate branches with hoses/tubing and quick-disconnect interfaces.

Reference — GF Piping Systems — GF whitepaper simulation

ParameterDocumented value / configuration
Port countA 44-branch manifold is used only as a stated simulation example, not as a family default.Conditions: branches: 44

Reference — GF Piping Systems — GF in-rack manifold

ParameterDocumented value / configuration
MaterialPVDF
Mountingtop feed; bottom feed
Flow distributionManufacturer describes uniform volume flow across outlet ports; validation remains configuration-specific.
Integrated componentsmain connections; branch ports; quick disconnects; optional air bleed; optional drain
Test conditions100% pressure tested with water before shipment; acceptance pressure/time are not stated in the sheet and must be agreed.

Reference — GF Piping Systems — 44-branch simulation

ParameterDocumented value / configuration
Pressure dropSimulation limit below 50 mbar per manifoldConditions: branches: 44; coolant: PG25; couplers: quarter-inch; temperature C: 30

Reference — GF Piping Systems — PVDF in-rack manifold / factsheet 04.26

ParameterDocumented value / configuration
Pressure designationPN10Conditions: Custom-engineered manufacturer reference, not site supply specification; limit: Nominal designation; allowable pressure depends on temperature, coolant and final assembly. Page 2 derating curve applies.
Temperature rangemaximum: 80; minimum: -20 °CConditions: Custom-engineered manufacturer reference, not site supply specification; limit: Datasheet temperature limits are not a rectangular PN10 operating envelope; consult page 2 pressure-temperature curve.
Component surface finishRa < 0.5 µmConditions: Custom-engineered manufacturer reference, not site supply specification; scope: Inner surfaces of injection-moulded and extruded components only, not a blanket complete-assembly roughness guarantee

Reference — AmpLink — XMF30S4

ParameterDocumented value / configuration
Section size30 x 30 mmConditions: Manufacturer reference only; not a site supply commitment; scope: Listed model column; weight is approximate, not an exact delivered assembly mass.
Tri clamp nominal size1 inConditions: Manufacturer reference only; not a site supply commitment; scope: Listed model column; weight is approximate, not an exact delivered assembly mass.
Estimated weight6 kgConditions: Manufacturer reference only; not a site supply commitment; scope: Listed model column; weight is approximate, not an exact delivered assembly mass.

Reference — AmpLink — XMF40S4

ParameterDocumented value / configuration
Section size40 x 40 mmConditions: Manufacturer reference only; not a site supply commitment; scope: Listed model column; weight is approximate, not an exact delivered assembly mass.
Tri clamp nominal size1-1/4 inConditions: Manufacturer reference only; not a site supply commitment; scope: Listed model column; weight is approximate, not an exact delivered assembly mass.
Estimated weight8 kgConditions: Manufacturer reference only; not a site supply commitment; scope: Listed model column; weight is approximate, not an exact delivered assembly mass.

Reference — AmpLink — XMF50S4

ParameterDocumented value / configuration
Section size50 x 50 mmConditions: Manufacturer reference only; not a site supply commitment; scope: Listed model column; weight is approximate, not an exact delivered assembly mass.
Tri clamp nominal size1-1/2 inConditions: Manufacturer reference only; not a site supply commitment; scope: Listed model column; weight is approximate, not an exact delivered assembly mass.
Estimated weight11 kgConditions: Manufacturer reference only; not a site supply commitment; scope: Listed model column; weight is approximate, not an exact delivered assembly mass.

Reference — AmpLink — XMF30S4 / XMF40S4 / XMF50S4

ParameterDocumented value / configuration
Material options304 / 316L stainless steelConditions: Manufacturer reference only; not a site supply commitment; scope: Manufacturer lists shared options; combinations must be checked against the selected configuration. Design pressure is not proof or burst pressure; temperature and derating are not stated.
Length options1870 / 2000 / 2130 mmConditions: Manufacturer reference only; not a site supply commitment; scope: Manufacturer lists shared options; combinations must be checked against the selected configuration. Design pressure is not proof or burst pressure; temperature and derating are not stated.
Branch count options12 / 18 / 24Conditions: Manufacturer reference only; not a site supply commitment; scope: Manufacturer lists shared options; combinations must be checked against the selected configuration. Design pressure is not proof or burst pressure; temperature and derating are not stated.
Coupling size optionsUQD 04 / 06 / 08Conditions: Manufacturer reference only; not a site supply commitment; scope: Manufacturer lists shared options; combinations must be checked against the selected configuration. Design pressure is not proof or burst pressure; temperature and derating are not stated.
Design pressure0.5 MPaConditions: Manufacturer reference only; not a site supply commitment; scope: Manufacturer lists shared options; combinations must be checked against the selected configuration. Design pressure is not proof or burst pressure; temperature and derating are not stated.
Branch hoseEPDM; 500 mm lengthConditions: Manufacturer reference only; not a site supply commitment; scope: Manufacturer lists shared options; combinations must be checked against the selected configuration. Design pressure is not proof or burst pressure; temperature and derating are not stated.

Candidate Product-family draft. Configuration, availability and acceptance are established for the requested item.

Component scope

Rack manifolds distribute supply and return coolant among branches. The port map, mounting envelope and connected devices must be defined together with the flow duty.

Configuration and selection

Prepare a numbered port map, connection schedule, supply/return identification, rack mounting and service access. State operating conditions, allowable pressure drop and any valves or sensors included in the assembly.

Define before quotation

  • Controlled drawing and design-authority boundary
  • Port map, mounting, attached components, and materials
  • Flow and pressure requirements
  • Inspection, leakage/proof test, cleanliness, documentation, and change control

Evidence and supply boundary

Exact model, interfaces, materials, coolant compatibility, operating conditions, tests, documentation, quantity and supply scope require configuration-specific review. No stock, certification or performance is implied by this draft.