Technical selection
Specifications and configuration
Reference — Parker Hannifin — family reference
| Parameter | Documented value / configuration |
|---|---|
| Interface | Push-in fittings with metal adapters are shown for server-to-cold-plate routing. |
| Interface | push-in tube; male thread; female thread; union; bulkhead; hose barb |
| Thread standard | NPTF; BSPT; BSPP; metric; UNF |
| Geometry | straight; elbow; tee; Y; reducer; bulkhead; cartridge |
Reference — Parker Hannifin — LIQUIfit
| Parameter | Documented value / configuration |
|---|---|
| Bore | D4 to D16 mm product range shown for LIQUIfit push-in fittings. |
| Sealing arrangement | LIQUIfit examples use an EPDM seal and stainless grab ring; seal and tube pairing must be checked by exact series. |
| Wetted material | bio-sourced nylon 11; EPDM seal; stainless steel grab ring |
| Working pressure | Up to 230 psi (16 bar), exact tubing/application dependent |
| Temperature | 1.7 to 93.3 degrees C (35 to 200 degrees F) |
Candidate Product-family draft. Configuration, availability and acceptance are established for the requested item.
Component scope
Fittings and adapters connect dissimilar ports, tubes, hoses and components within a defined coolant loop. A matching nominal size does not establish thread, seat or sealing compatibility.
Configuration and selection
Name both end interfaces and sealing methods, passage geometry, material, coolant, envelope and the neighbouring components. Check working conditions and leak-test requirements for the assembled connection.
Define before quotation
- Port, thread, tube, or hose interface
- Geometry, orientation, and envelope
- Wetted material and finish
- Pressure, leakage, cleanliness, and documentation requirements
Evidence and supply boundary
Exact model, interfaces, materials, coolant compatibility, operating conditions, tests, documentation, quantity and supply scope require configuration-specific review. No stock, certification or performance is implied by this draft.