Technical selection
Specifications and configuration
Reference — BEEHE GB200 node manifold reference
| Parameter | Documented value / configuration |
|---|---|
| Branch interface count | Two branches listed in the GB200 column |
| Envelope dimensions | 431.6 × 64.5 × 30.2 mm listed in the GB200 column |
| Body pipe material | SUS304 body and SUS316 piping listed in the GB200 column |
| Supply distribution mode | Manufacturer describes the inner-manifold family as generally using one inlet to distribute to multiple outlets; the GB200 column separately lists two branches. Exact supply/return pairing for a pictured build requires a drawing.Conditions: scope: General manufacturer description, not a GB200 order-code hydraulic schematic or claim that both pictured legs are supply outlets |
| Mounting method | Screw mounting, as listed in the GB200 platform columnConditions: scope: Platform-column reference; hole pattern and mounting datums are not published |
| Branch external interfaces | NVQD04 branch interface and NVQD04 external interface, as listed in the GB200 platform columnConditions: scope: Interface designations only; actual mating part numbers and revision require drawing confirmation |
| Manufacturer pressure reference | 10 bar stated as pressure-bearing reference in the GB200 platform columnConditions: scope: Manufacturer table only; working/test/burst basis and temperature/coolant conditions are not defined. Not a site supply or complete-loop rating |
Manufacturer series reference. Confirm the exact order code, mating parts and stated conditions for the quoted configuration.
Overview
This two-branch node assembly is a different routing and interface purchase from the wide many-port header. It fits a narrower server-internal distribution role when matched to an approved chassis design.
Construction and interfaces
The second manufacturer gallery image depicts two slim corrugated branches with end fittings. The GB200 reference column lists SUS304 body material and SUS316 piping for its configuration.
Selection
The GB200 column lists two branches, NVQD04 at both the branch and external interfaces, screw mounting and a 431.6 × 64.5 × 30.2 mm envelope. The maker describes the inner-manifold family as generally distributing one inlet to multiple outlets; confirm the exact supply/return circuit, mating revisions, datums and clearances on a controlled drawing.
Configuration options
Confirm the mating quick-disconnect halves, mounting-hole pattern and tubing route for the ordered configuration. Do not treat one gallery image as a dimensioned or final installed assembly.
Application limits
The GB200 table states 10 bar as a pressure-bearing reference but gives no working/test/burst basis or temperature and coolant conditions. It is not a site or installed-loop rating. A platform label is not an order code or a claim of fit to every GB200 system; seal and leak-acceptance conditions remain configuration-specific.