Reference — Motivair direct-to-chip hose kits
| Parameter | Documented value / configuration |
|---|---|
| Documented loop connections | In-rack manifold to server; in-rack manifold to CDU or HDUConditions: scope: Motivair page description, not an assurance of a particular terminal fitting |
| Assembly construction | Custom hosing paired with dripless quick connectsConditions: scope: manufacturer family description; selected hose, QD and mating half require drawing |
| Listed diameter options | 3/16, 1/2, 3/4, 1 and 2 inchesConditions: scope: manufacturer listed options; not all lengths and fittings can be assumed for every diameter |
| Configurable length | Hose kit length and diameter can be customizedConditions: scope: quote/drawing input; no standard length or tolerance provided |
| Listed options | Tight bend radius, colour coding and plenum-rated option for underfloor useConditions: scope: manufacturer feature list; exact option availability and material certification require selected configuration |
| Manufacturer test statement | Factory pressure testedConditions: scope: manufacturer statement; test pressure, dwell time and acceptance must be specified |
Manufacturer series reference. Confirm the exact order code, mating parts and stated conditions for the quoted configuration.
Overview
This configured hose-kit type connects a rack manifold to a server or other direct-to-chip liquid loop. The pictured manufacturer reference shows a complete hose with two dissimilar connector ends, so both interfaces must be specified rather than assuming a plain cut hose.
Construction and interfaces
Motivair describes configurable hosing paired with dripless quick connects. The photographed ends illustrate one arrangement, not a universal quick-disconnect standard, wetted-material declaration or known order code.
Selection
Choose a route and finished length that respect the installed bend envelope and access to both mating connectors. The manufacturer lists several diameter options, but does not state that every end fitting and bend configuration is available at every diameter.
Configuration options
Documented choices include configurable length and diameter, colour coding and a plenum-rated option for underfloor use. Select hose construction, both connector series, colour, orientation, cleaning and packaging through an approved drawing and quotation.
Application limits
The source says hose kits are factory pressure-tested but does not supply the test pressure, dwell or pass criterion on this page. No working pressure, coolant compatibility or certification is inferred from the picture or feature list.