Leak Detection Components
TTK Multi-Circuit Liquid Leak Detection Controller
A separately housed leak-detection panel that monitors sensing-cable circuits and provides alarm outputs; the device is an exact model reference, not a complete site shutdown system.
- Coverage
- location accuracy m: 1; maximum per circuit m: 600; maximum total m: 1800
- Output
- eight programmable alarm relays; power-fail relay; Modbus over RS232/RS422/RS485
- Alarm boundary
- Panel reports leak or cable-break state; site shutdown/interlock logic remains a separate system design decision.
- Test method
- Built-in test function scans the system and connected cable lengths; commissioning acceptance needs a documented procedure.
TTK
Leak Detection Components
Specifications apply to the named product and stated configuration; final supply details are agreed in the quote.