Quick Disconnect Couplings
Envicool Clamp-Retained Quick Disconnect
A CGS direct-insertion coupling pair with an additional clamp-retention concept and size-specific hydraulic catalogue rows, shown in an official series rendering.
- Engagement mechanism
- Clamp-fastened push-to-lock coupling | Conditions: supplier series structure; not an installed vibration certification
- Listed temperature range
- -55 to 120 degC | Conditions: series summary; verify pressure and fluid for exact seal variant
- Size specific recommended flow
- CGS03 2.1; CGS05 5.88; CGS08 15; CGS10 23.55; CGS12 33.9; CGS15 53; CGS20 94.2 L/min | Conditions: separate model rows, water 20 degC, plug-to-socket, 5 m/s velocity criterion; not one family rating
- Ordering structure
- Socket and plug codes, end connections and dimensions are tabulated separately | Conditions: exact mating pair and end form to be specified; drawing governs
Envicool
Quick Disconnect Couplings
Specifications
CGS series
| Parameter | Documented value / configuration |
|---|---|
| Size specific socket plug end examples | The CGS03 socket table includes a stainless-code G1/8 male-thread example CGS03.1342-G18; the plug table separately lists 4 and 6 mm clamp-fastened hose-end examples, so the two ends must be ordered separatelyConditions: Illustrative series options, not a pre-validated compatible pair or a port claim for the configuration |
| Listed shell and seal options | CGS order-code tables separate aluminum-alloy and stainless-steel versions; series summary lists EPDM and FVMQ sealing-ring optionsConditions: Selected material and seal follow exact order codes and require coolant review |
Specifications apply to the named product and stated configuration; final supply details are agreed in the quote.